|T88 Temperature Regulating Valve|TL10H Temperature Regulating Valve|
|BW5 Temperature Regulating Valve
|Wax Type Temperature Regulating Valve
| |
■T88 Temperature Regulating Valve (387KB) |
|
For heat exchanger and hot water storage tank
Size : 15〜150A
Fluid : | Steam(flow through body)
|
Hot/cold water(for bulb)
|
Max. pressure : 0.2〜1.0MPa
Max. temperature : 185℃(flow through body)
Control temperature rage : 15〜120℃
Material : | BodyーFC
|
Valve disc/seatーSUS
|
Connection : | Body-Flanged
|
Bulb-Pipe threaded(Flanged on request)
|
• | Sharp functioning
|
• | Precise temperature setting
|
| |
|
| | |
|
|
■TL10H Temperature Regulating Valve (203KB) |
|
For oil pre-heater and small sized hot water storage tank
Size : 15〜50A
Fluid : | Steam, hot/cold water(flow through body)
|
Heavy oil, hot water(for bulb)
|
Max. pressure : 1.0MPa
Max. temperature : 185℃(flow through body)
Control temperature rage : 15〜110℃
Material : | BodyーFCD
|
Valve disc/seatーSUS
|
Connection : | Body-Flanged
|
Bulb-Pipe threaded
|
• | Light and compact
|
• | Best for heating heavy oil and water.
|
| |
|
| | |
|
|
■BW5 Temperature Regulating Valve (626KB) |
|
For heat exchanger and hot water storage tank
Main valve : P260, Size : 15〜150A
Pilot valve : TL10H, Size : 15A
Fluid : | Steam(flow through body of main valve)
|
Hot/cold water(for bulb)
|
Max. temperature : 220℃(for main valve)
Control temperature rage : 15〜110℃
Material : | Main valve : | BodyーFC
|
Valve disc/seatーSUS
|
Pilot valve : | BodyーFCD
|
Valve disc/seatーSUS
|
Connection : | Body-Flanged
|
Bulb-Pipe threaded
|
• | Pilot operated
|
• | Temperature and pressure is regulated simultaneously.
|
| |
|
| | |
|
|
■Wax Type Temperature Regulating Valve (934KB) |
|
For air conditioning, chiller, cooling tower
Size : 25〜250A
Fluid : Hot water, cooling water, lube oil, fuel oil
Max. pressure : 1.0MPa
Max. temperature : Set point plus 20℃(Max.115℃)
Material : BodyーFC
Connection : Flanged
• | Light and compact
|
• | Economical
|
• | Can be installed horizontally or vertically.
|
• | Operation is not affected by the surrounding temperature.
|
• | Maintenance & repair can be done without removing from piping.
|
| |
|
| | |
|
|
To the top of this page |
|